How many code violations? Part 5

2 years ago
58

#Shorts
Electric Pro Academy - Real skills to make real money.

How many code violations can you spot in this disconnect? We found:
Upside-Down Breaker [NEC 240.33 & 240.81]
Missing Bonding Bushing On The Lower Conduit Entry [NEC 250.92 & 408.3(C)]
No Interior Dead Front [NEC 110.27(A)]
Improper Termination Labels [NEC 200.6 & 210.5(C)]
Indiana is only responsible for NEC 2008, but we’re always working to keep ourselves educated on the latest edition as well! Let us know if you notice any others!

Want to be in a YouTube Short? Send us your electrical questions in 10 seconds or less and we’ll splice in a master electrician’s less than 50 second answer (as best as we can). If this short is unclear or skew to what you are looking for, feel free to comment below for additional assistance. Got a question or ideas for a future video? Leave a comment below and submit your idea here: https://forms.clickup.com/f/23xa9-70/MU8E4HBGPNY3NXVQA3

Thank you for watching; we value your feedback and monitor this channel daily.

Connect With Us:
Electric Pro Academy is a multimedia team dedicated to training and instructing DIYers and professional electricians for the growth and dignity of the craft nationwide.
https://www.instagram.com/ElectricProAcademy/
https://www.facebook.com/ElectricProAcademy
https://odysee.com/@ElectricPro

Jefferson Electric installs and services residential, commercial, solar, and Tesla systems in Indianapolis, IN.
https://www.jeffersonelectricllc.com/
https://www.facebook.com/JeffersonElectric
https://www.linkedin.com/company/jefferson-electric-llc/

Loading comments...