How many code violations? Part 5

1 year ago
52

#Shorts
Electric Pro Academy - Real skills to make real money.

How many code violations can you spot in this disconnect? We found:
Upside-Down Breaker [NEC 240.33 & 240.81]
Missing Bonding Bushing On The Lower Conduit Entry [NEC 250.92 & 408.3(C)]
No Interior Dead Front [NEC 110.27(A)]
Improper Termination Labels [NEC 200.6 & 210.5(C)]
Indiana is only responsible for NEC 2008, but we’re always working to keep ourselves educated on the latest edition as well! Let us know if you notice any others!

Want to be in a YouTube Short? Send us your electrical questions in 10 seconds or less and we’ll splice in a master electrician’s less than 50 second answer (as best as we can). If this short is unclear or skew to what you are looking for, feel free to comment below for additional assistance. Got a question or ideas for a future video? Leave a comment below and submit your idea here: https://forms.clickup.com/f/23xa9-70/MU8E4HBGPNY3NXVQA3