Trane Intellipak I Compressor Circuit Trip Troubleshooting Diagnostic
YOU are responsible for receiving proper SAFETY and DIAGNOSTIC and REPAIR training! KNOW PROPER Lock Out Tag Out procedures! WEAR proper PPE! Please work safely and do not rush. This video is meant for HVAC technicians that are properly licensed and insured or work for licensed and insured companies! Watching this video does not in itself qualify you to work on this equipment. It is only meant to be a guide for those in the industry that are also following safe working procedures!
1) Verify proper airflow across the condenser. Check ALL condenser fan motors, fan blades, and wiring. Check for dirty condenser coils. Verify proper condenser temperature thermistor readings.
2) Check for tripped compressor circuit breakers. If they’re tripped, check for a short to ground and a short across windings. If no short is detected with your multimeter, use a megger. (WARNING: Get proper training on how to use a megger to avoid INJURY or equipment DAMAGE!) If no short is detected, check for LRA. If the compressors check out, verify that the compressor circuit breaker is operating properly. If the compressor circuit breaker is NOT tripped, ensure the compressor circuit breaker auxiliary is operating properly. (N.O. means the Aux is open when the breaker is off or tripped.)
3) Check the 1F44 and 1F45 fuses, their contact in the socket, and their wiring.
4) Check the compressor module (in the compressor mounted junction box) for proper operation. Verify the compressor module thermistor is working properly. If desired, buy the adapter tool from Trane Parts and connect with your Android phone. Download the INTspector app to your Android device.
5) If you cannot pinpoint the cause of the diagnostic, install a *** fast acting 50 mA 250 VAC indicating fuse *** in PARALLEL with the safeties in this specific circuit. (See the Compressor Module wiring schematic. HPS, Compressor Module M1-M2, and Compressor Circuit Breaker Aux Switch.) If a safety opens even briefly, the 50 mA fuse cannot handle the load of the circuit and will open. When you return, locate the blown fuse and that’s the safety that’s opening. Verify if the safety is working properly or if the safety is faulty and remedy the problem. DO NOT use a higher rated fuse as this may bypass a safety possibly resulting in equipment damage!
-
1:29:23
Glenn Greenwald
8 hours agoMarco Rubio, Europe Thwart Ukraine Peace Deal; NSA Illegally Leaks Steve Witkoff's Diplomatic Calls; Bari Weiss's Comically Out of Touch Plan for CBS | SYSTEM UPDATE #550
149K90 -
51:15
State of the Second Podcast
10 hours agoCan You Trust Paid Gun Reviews? (ft. Tactical Advisor)
31.2K3 -
8:56
MetatronGaming
8 hours agoSuper Nintendo NA vs PAL
36.7K8 -
20:02
Scammer Payback
10 hours agoHijacking a Scammer Group's Live Video Calls
16.1K4 -
3:18:30
Nikko Ortiz
8 hours agoArc Raiders 1st Gameplay... | Rumble LIVE
43.2K2 -
2:17:05
Blabs Life
9 hours agoPART 3: Peter Jackson's King Kong: The Official Game of the Movie | Noob Plays
28.2K2 -
18:07
MetatronCore
7 hours agoAmala Ekpunobi is BASED
24.7K7 -
1:01:48
BonginoReport
8 hours agoWaddle & Gobble Receive Presidential Pardons! - Nightly Scroll w/ Hayley Caronia (Ep.185)
128K32 -
53:41
Katie Miller Pod
7 hours agoMike & Kelly Johnson on Marriage, Family, & Demands of the Job | The Katie Miller Podcast Ep. 16
47.6K15 -
1:31:04
The Daily Signal
8 hours ago $5.77 earned🚨BREAKING: Judicial CHAOS—$7 Million Somalian Fraud Scandal Thrown Out, Trans Terrorist Released
32.1K11